Level Controller Topic: Simple Liquid Level Detection without Pump Control

 

FAQ No. FAQ00701

 

Question

 

Which Controller model is best for simple liquid-level detection without pump control?
 


Answer

61F-GP-N Floatless Level Controller is suitable.


Prepare the same number of 61F-GP-N Controllers as the number of liquid-level detection points.
 

 

Connection Diagram
 

Note: The common electrode (longest electrode), terminal 4, can be shared by matching the power supply phases (between terminals 3 and 9).

Principles of Operation:

  • If the water level reaches E3, the lower-limit 61F-GP-N Controller’s LED indicator goes ON, terminals 6 and 7 close, and terminals 10 and 11 close.

  • If the water level reaches E2, the midpoint 61F-GP-N Controller’s LED indicator goes ON, terminals 6 and 7 close, and terminals 10 and 11 close.

  • If the water level reaches E1, the upper-limit 61F-GP-N Controller’s LED indicator goes ON, terminals 6 and 7 close, and terminals 10 and 11 close.
     

 