FAQ No. FAQ01969
Question
What are the conditions for detecting disconnection for
G3PX-2[][]EHN-CT Power Controllers that detect disconnection for multiple heaters?
Answer
The disconnection detection conditions are listed below.
1. The load current must be 1 A min.
2. The CT detection current must be 30% or higher of the rated maximum
load current.
Note: Increase the number of CT turns if the
CT detection current is 30% or less.
3. Up to five heaters can be connected (20% multiple heater disconnection
detection characteristics)

Care must be taken because the following phases are not detected by heater