Features:

Programless Communication with PLC

 

Easy Interaction with HMI

 

Modular Design and Easy Expansion

 

Control System with Higher Functionality

 

Demo on Setup using CX-Thermo

 

System Configurations

 

Application Examples

 

Multi-loop Control System
 

  Main Feature 4: 

 

Control System with Higher Functionality

 

High sampling speed, Current Transformer input for better control and performance.
Direct connection of G3ZA Multi-channel Power Controller provides optimum cycle control for high accuracy regulation with minimal noise.

 

 

High Speed Sampling

 

High sampling cycle of 250ms per channel
Ideal for application requiring quick response to temperature increases.

 

High-speed startup in jsut a few seconds.

 

 

High Current Transformer Input
 

Heater Burnout alarms up to 100A.
Ideal for controlling high-capacity heaters.
SSR failure alarms and heater overcurrent alarms can also be used.

 

CT input : 100 A

 

 

Multi-Input

 

EJ1 Unit accepts thermocouple, platinum-resistance thermometer, and analogue input, thus reduce stock inventory and selection worries.

 

Easy to select. Reduced inventory.

 

Output ON Scheduling

 

The ON time for each output can be reduced to ½ or ¼ of the control period to limit the number of outputs in the Unit that are being turn ON simultaneously.
 

 

Output ON Scheduling Chart

The Output ON scheduling function reduces the overall current consumes by the heaters, thus reducing the size of power supply.
 

 

 

Optimum Cycle Control

 

Eight unit of G3ZA Multi-channel Power Controller can be directly connected to one EJ1 unit to create high-accuracy regulation with low noise to ensure optimum cycle control.
 

Enables smaller panels than power controllers. Control up to 8 SSRs with one Unit.

 

Conventional Control Method Optimum Cycle Control Method

Cycle control (zero cross ON/OFF control)

• The control cycle is long, and so control performance is poor.
• Little noise is generated.

Cycle control (zero cross ON/OFF control) chart

Phase control
• Response is fast, and so high-accuracy temperature control is possible.
• Higher harmonics and noise are issues.

Phase control chart

Optimum Cycle Control (high accuracy zero cross control)


• ON/OFF is determined every half cycle.


• Noise generation is suppressed and response is fast, enabling high-accuracy temperature control.

Optimum Cycle Control (high accuracy zero cross control) chart

 

 

Compliance to RoHS

 

The EJ1 has already eliminated the use of the six hazardous chemical substances, including lead and mercury in response to RoHS directive.

 

Removal of 6 hazardous substances

 

 

 