CS-series EtherNet/IP Unit
last update: May 20, 2024
| Item | Specifications | |
|---|---|---|
| Model number | CS1W-EIP21/EIP21S | |
| Type | 100Base-TX *1 | |
| Applicable PLCs | CS-series PLCs *2 | |
| Unit classification | CS-series CPU Bus Unit | |
| Mounting location | CPU Rack or Expansion Rack | |
| Number of Units that can be
mounted |
8 max. (including Expansion Racks) | |
| CPU
Unit words used |
Allocated CIO Area
words (CPU Bus Unit words) |
25 words/Unit (one unit number’s words) |
| These words contain control bits and flags, the target node PLC’s operating and
error information, Unit status, communications status, registered/normal target node information, and FINS/TCP connection status. |
||
| Allocated DM Area
words (CPU Bus Unit words) |
100 words/Unit (one unit number’s words) | |
| These words contain the IP address display/setting area | ||
| User-set area | Any usable data area words | |
| Target node PLC’s operating and error information, and registered/normal target
node information |
||
| CPU Bus Unit System
Setup |
Not used. | |
| Non-volatile memory within
EtherNet/IP Unit (See note.) |
The following settings are stored in the EtherNet/IP Unit’s non-volatile memory.
Note: Unlike the regular Ethernet Units, the CPU Bus Unit Setup Area in the CPU Unit is not used for these settings. 1. Unit setup (communications settings for the EtherNet/IP Unit, such as the IP address, DNS server settings, host name, baud rate, FINS/UDP settings, and FINS/ TCP settings) 2. Tag data link settings (device parameters) 3. User authentication settings (CS1W-EIP21S only) 4. Operation log (CS1W-EIP21S only) |
|
| Transfer
specifi- cations |
Media access method | CSMA/CD |
| Modulation method | Baseband | |
| Transmission paths | Star form | |
| Baud rate | 100 Mbit/s (100Base-TX) | |
| Transmission media | Shielded twisted-pair (STP) cable
Categories: 100 Ω at 5, 5e |
|
| Transmission distance | 100 m (distance between hub and node) | |
| Number of cascade
connections |
There is no limitation when a switching hub is used. | |
| Current consumption (Unit) | CS1W-EIP21: 410 mA max. at 5 V DC
CS1W-EIP21S: 620 mA max. at 5 V DC |
|
| Weight | CS1W-EIP21: 171 g max.
CS1W-EIP21S: 180 g max. |
|
| Dimensions | 35 × 130 × 101mm (W × H × D) | |
| Other general specifications | Other specifications conform to the general specifications of the CS-series | |
*1. If tag data links are being used, use 100Base-TX. Otherwise, 10Base-T can be used, but this is not recommended.
*2. For the CS1W-EIP21S, the following CPU Units are supported.
CS1G-CPU[][]H, CS1H-CPU[][]H, CS1D-CPU[][]HA/H, CS1D-CPU[][]SA/S, and CS1D-CPU[][]P
| Item | Specifications | ||
|---|---|---|---|
| CIP
service |
Tag data
links (Cyclic communi- cations) |
Number of connections | 256 |
| Packet interval
(refresh cycle) |
0.5 to 10,000 ms (in 0.5-ms units)
Can be set independently for each connection. (Data is refreshed over the network at the preset interval and does not depend on the number of nodes.) |
||
| Allowed
communications bandwidth per Unit |
6,000 to 12,000 pps *1 *2
Note: Including the heartbeat. |
||
| Number of tag sets | 256 | ||
| Tag types | CIO Area, DM Area, EM Area, Holding Area, and Work Area | ||
| Number of tags per
connection (= 1 tag set) |
8 (7 tags when the tag set contains the PLC status) | ||
| Maximum link data size per node
(total size of all tags) |
184,832 words | ||
| Maximum data size per
connection |
252 words or 722 words *3
Note: Data synchronicity is maintained within each connection. |
||
| Number of registrable
tag sets |
256
(1 connection = 1 tag set) |
||
| Maximum size of 1 tag
set |
722 words
(The PLC status uses 1 word when the tag set contains the PLC status.) |
||
| Maximum number of
tags that can be refreshed per CPU Unit cycle *4 |
Output/Transmission (CPU to EtherNet/IP): 19
Input/Reception (EtherNet/IP to CPU): 20 *5 |
||
| Data that can be
refreshed per CPU Unit cycle *4 The layout of the allocated CIO Area words is the defauly *6 |
Output/Transmission (CPU to EtherNet/IP): 7,469 words
Input/Reception (EtherNet/IP to CPU): 7,469 words |
||
| Changing tag data link
parameters during operation |
Supported *7 | ||
| Multicast packet filter
function *8 |
Supported | ||
| Explicit
messaging |
Class 3 (connected) | Number of connections: 128 | |
| UCMM (unconnected) | Number of clients that can communicate at one time: 32 max.
Number of servers that can communicate at one time: 32 max. |
||
| CIP routing | CS1W-EIP21/EIP21S, CJ1W-EIP21/EIP21S,
CJ2H-CPU6[]-EIP, CJ2M-CPU3[] |
||
| FINS service *9 | FINS/UDP | Supported | |
| FINS/TCP | 16 connections max. | ||
| SNMP | Agent | SNMPv1, SNMPv2c, SNMP trap | |
| MIB | MIB-II | ||
| EtherNet/IP conformance test | CS1W-EIP21S: CT17
CS1W-EIP21: CT11 |
||
| Ethernet interface | 10BASE-T or 100BASE-TX
Auto Negotiation or fixed settings |
||
*1. In this case, pps means "packets per second" and indicates the number of packets that can be processed in one
second.
*2. When using CS1W-EIP21S or CS1W-EIP21 with version 3.0 or later.
When using CS1W-EIP21 with version 2.1 or earlier, the allowed communications bandwidth per Unit is 6,000 pps.
| Condition | Output/Transmission | Input/ Reception |
|---|---|---|
| CS1W-EIP21S | 18 | 18 |
| CS1W-EIP21 | 19 | 19 |
*6. The table below shows value when the layout type is User defined.
| EIP21 | EIP21S | ||
|---|---|---|---|
| Data (words) that can be refleshed
per CPU Unit cycle |
Output/Transmission | 7405 | 7321 |
| Input/Reception | 7405 | 7385 | |
*7. If parameters are changed in the EtherNet/IP Unit, however, the EtherNet/IP Unit will be restarted. When other nodes are communicating with the affected node, the communications will temporarily time out and automatically recover later.
*8. Because the EtherNet/IP Unit is equipped with an IGMP client, unnecessary multicast packets can be filtered by using a switching hub that supports IGMP snooping.
*9. The EtherNet/IP Unit uses the TCP/UDP port numbers shown in the following table.
| Service | Protocol | Port number | Remarks |
|---|---|---|---|
| Tag data links | UDP | 2222 | The port number is fixed. |
| Class 3, UCMM | TCP/UDP | 44818 | |
| DNS | UDP | 53 | |
| Secure Comm | TCP | 443 | The port number is fixed.
It is supported by the CS1W-EIP21S only. |
| FINS/UDP service | UDP | 9600 | Port numbers in the Unit Setup can be changed with
the CX-Programmer. |
| FINS/TCP service | TCP | 9600 | |
| FTP | TCP | 20, 21 | |
| SNTP | UDP | 123 | |
| SNMP | UDP | 161 | |
| SNMP trap | UDP | 162 |
The Network Configurator is a software package designed for building, setting, and controlling a multi-vendor EtherNet/IP Network using OMRON's EtherNet/IP. It is included in CX-One.
CS1W-EIP21 EtherNet/IP Unit. Network Configurator version 3.0 or higher is included with CX-One version 3.0 or higher.
CS1W-EIP21S EtherNet/IP Unit. Network Configurator version 3.74a or higher is included with CX-One version 4.61 or higher.
The Network Configurator provides the following functions for building, setting, and controlling EtherNet/IP.
| Item | Specification | ||
|---|---|---|---|
| System Requirements | Refer to the CX-One Catalog (Cat. No. R134), visit your local OMRON website. | ||
| Network
connection method |
CS1/CJ1 | CJ2 | |
| Serial interface | CPU Unit’s Peripheral or RS-232C port | CPU Unit’s USB or RS-232C port | |
| Ethernet interface | EtherNet/IP Unit’s Ethernet port | CPU Unit’s Ethernet port
EtherNet/IP Unit’s Ethernet port |
|
| Location on Network | A single node address is used (only when directly connected to EtherNet/IP). | ||
| Number of Units that can be
connected to Network |
A single Network Configurator per Network
(More than one Configurator cannot be used in the same system.) |
||
| Main
functions |
Network control
functions |
•The Network configuration can be created and edited regardless of whether the
Network Configurator is online or offline. •The Network configuration can be read from a file or the network. |
|
| Configuration
functions |
The EDS files used by the Network Configurator can be installed and deleted. | ||
| Supported file formats | Configurator network configuration files (*.ncf)
Configuration files (*.ncf) created using the Network Configurator for EtherNet/IP (version 2) can be imported by selecting External Data - Import from the File Menu. |
||
last update: May 20, 2024