Power Relays
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: November 20, 2013
| Item |
Rated current (mA) |
Coil resistance (Ω) |
Must operate voltage (V) |
Must release voltage (V) |
Maximum voltage allowable (V) |
Power consumption (VA, W) |
||
|---|---|---|---|---|---|---|---|---|
| Rated voltage (V) | 50 Hz | 60 Hz | Percentage of rated voltage | |||||
| AC | 24 | 110 | 96.3 | 48.4 | 80% max. | 30% min. at 60 Hz 25% min. at 50 Hz |
110% | Approx. 2.3 VA at 60 Hz Approx. 2.7 VA at 50 Hz |
| 100 | 26.6 | 23.1 | 760 | |||||
| 110 | 24.2 | 21.0 | 932 | |||||
| 120 | 22.2 | 19.3 | 1,130 | |||||
| 200 | 13.3 | 11.6 | 3,160 | |||||
| 220 | 12.1 | 10.5 | 3,550 | |||||
| 230 | 11.5 | 10.0 | 4,250 | |||||
| 240 | 11.0 | 9.6 | 4,480 | |||||
| DC | 12 | 126 | 95 | 15% min. | Approx. 1.5 W | |||
| 24 | 63.2 | 380 | ||||||
| 48 | 32.0 | 1,500 | ||||||
| 110 | 13.6 | 8,060 | ||||||
| 220 | 6.8 | 32,200 | ||||||
| Load | Resistive
load |
Inductive load | Resistive
load |
Inductive load | |||
|---|---|---|---|---|---|---|---|
| L/R = 7 ms | DC13 class | L/R = 7 ms | DC13 class | ||||
| Contact configuration | NO | Double-break | Double-break | ||||
| NC | --- | Single-break | |||||
| Contact material | AgSnIn | AgSnIn | |||||
| Rated load | NO | 10 A,
220 VDC |
5 A,
220 VDC |
0.4 A,
220 VDC |
5 A,
220 VDC |
3 A,
220 VDC |
0.2 A,
220 VDC |
| NC | --- | 2 A,
220 VDC |
0.3 A,
220 VDC |
0.1 A,
220 VDC |
|||
| Rated carry current | NO | 10 A | 5 A | ||||
| NC | --- | 2 A | |||||
| Max. switching voltage | NO | 220 VDC | 220 VDC | ||||
| NC | --- | ||||||
| Max. switching current | NO | 10 A | 5 A | 0.4 A | 5 A | 3 A | 0.2 A |
| NC | --- | 2 A | 0.3 A | 0.1 A | |||
| Max. switching capacity
(reference value) |
NO | 2,200 W | --- | --- | 1,100 W | --- | --- |
| NC | --- | 440 W | --- | --- | |||
| Contact form | SPST-NO | SPST-NO/SPST-NC | |
|---|---|---|---|
| Model | MKS1T(I)(N)-10 | MKS2T(I)(N)-11 | |
| Load | Resistive load | Resistive load | |
| Contact configuration | NO | Double-break | Double-break |
| NC | --- | Single-break | |
| Contact material | AgSnIn | AgSnIn | |
| Rated load | NO | 15 A, 250 VAC | 15 A, 250 VAC |
| NC | --- | 5 A, 250 VAC | |
| Rated carry current | NO | 15 A | 15 A |
| NC | --- | 5 A | |
| Max. switching voltage | NO | 250 VAC | 250 VAC |
| NC | --- | ||
| Max. switching current | NO | 15 A | 15 A |
| NC | --- | 5 A | |
| Max. switching capacity (reference value) | NO | 3,750 VA | 3,750 VA |
| NC | --- | 1,250 VA | |
* These values apply to a switching frequency of 20 times per minute.
| Contact resistance *1 | 100 mΩ max. | |
|---|---|---|
| Operate time *2 | AC: 20 ms max.
DC: 30 ms max. |
|
| Release time *2 | 20 ms max. | |
| Max.
operating frequency |
Mechanical | 18,000 operations/h |
| Rated load | Models for DC loads: 1,800 times/hour
Models for AC loads: 1,200 times/hour |
|
| Insulation resistance *3 | 100 MΩ min. | |
| Dielectric
strength |
Between coil and contacts | 2,500 VAC 50/60 Hz for 1 min between |
| Between contacts of
different polarity |
2,500 VAC 50/60 Hz for 1 min between | |
| Between contacts of same
polarity |
1,000 VAC 50/60 Hz for 1 min | |
| Vibration
resistance |
Destruction | 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude) |
| Malfunction | 10 to 55 to 10 Hz, 0.50-mm single amplitude (1.0-mm double amplitude) | |
| Shock
resistance |
Destruction | Back-connecting Socket (P7M-06P) mounting: 1,000 m/s2
Front-connecting Socket (P7MF-06(-D)) mounting:500m/s2 |
| Malfunction | 100 m/s2 | |
| Endurance | Mechanical | 1,000,000 operations min. (at 18,000 operations/hr) |
| Electrical *4 | 100,000 operations min. (at rated load and maximum switching frequency) | |
| Failure rate P level (reference value) | 10 mA at 24 VDC | |
| Ambient operating temperature | -40 °C to 60 °C (with no icing or condensation)
Note: The range is -25 °C to 60 °C for models with built-in operation indicators. |
|
| Ambient operating humidity | 5% to 85% | |
| Weight | SPST-NO: Approx. 73 g, SPST-NO/SPST-NC: Approx. 82 g | |

| Model | Coil ratings | Contact ratings | Operations | |
|---|---|---|---|---|
| MKS1XT[]-[] | 12 to 220 VDC
24 to 240 VAC |
NO contacts | 10 A, 220 VDC (Resistive)
5 A, 220 VDC L/R (T0.632) = 7 ms 0.4 A, 220 VDC L/R (T0.95) = 300 ms |
6,000 |
| MKS2XT[]-[] | NO contacts | 5 A, 220 VDC (Resistive)
3 A, 220 VDC L/R (T0.632) = 7 ms 0.2 A, 220 VDC L/R (T0.95) = 300 ms |
||
| NC contacts | 2 A, 220 VDC (Resistive)
0.3 A, 220 VDC L/R (T0.632) = 7 ms 0.1 A, 220 VDC L/R (T0.95) = 300 ms |
|||
| MKS1T[]-[] | NO contacts | 15 A, 250 VAC (Resistive) | ||
| MKS2T[]-[] | NO contacts | 15 A, 250 VAC (Resistive) | ||
| NC contacts | 5 A, 250 VAC (Resistive) | |||
: CSA C22.2 No.14

| Model | Coil ratings | Contact ratings | Operations | |
|---|---|---|---|---|
| MKS1XT[]-[] | 12, 24, 48, 110, 220 VDC
24, 100, 110, 120, 200, 220, 230, 240 VAC |
NO contacts | DC-1: 10 A, 220 VDC
5 A, 220 VDC L/R (T0.632) = 7 ms DC-13: 0.4 A, 220 VDC |
100,000 |
| MKS2XT[]-[] | NO contacts | DC-1: 5 A, 220 VDC
3 A, 220 VDC L/R (T0.632) = 7 ms DC-13: 0.2 A, 220 VDC |
||
| NC contacts | DC-1: 2 A, 220 VDC
0.3 A, 220 VDC L/R (T0.632) = 7 ms DC-13: 0.1 A, 220 VDC |
|||
| MKS1T[]-[] | NO contacts | AC-1: 15 A, 250 VAC 50/60 Hz | ||
| MKS2T[]-[] | NO contacts | AC-1: 15 A, 250 VAC 50/60 Hz | ||
| NC contacts | AC-1: 5 A, 250 VAC 50/60 Hz | |||
last update: November 20, 2013