Motor Protection Circuit Breaker (MPCB)
last update: February 3, 2014
Rated
current In A |
Suitable
for motors *1 3~400V kW |
Current setting range | Short-
circuit breaking capacity at 3~400V kA |
Type | Pack
pcs. |
Weight
approx. kg/pcs. |
||
---|---|---|---|---|---|---|---|---|
Thermal
overload release A |
Instantaneous
short-circuit release A |
|||||||
Circuit-Breakers J7MN-12 | ||||||||
0.16 | - | 0.11 - 0.16 | 2.1 | 100 | J7MN-12-E16 | 1 | 0.21 | |
0.2 | - | 0.14 - 0.2 | 2.6 | 100 | J7MN-12-E2 | 1 | 0.21 | |
0.25 | 0.06 | 0.18 - 0.25 | 3.3 | 100 | J7MN-12-E25 | 1 | 0.21 | |
0.32 | 0.09 | 0.22 - 0.32 | 4.2 | 100 | J7MN-12-E32 | 1 | 0.21 | |
0.4 | - | 0.28 - 0.4 | 5.2 | 100 | J7MN-12-E4 | 1 | 0.21 | |
0.5 | 0.12 | 0.35 - 0.5 | 6.5 | 100 | J7MN-12-E5 | 1 | 0.21 | |
0.63 | 0.18 | 0.45 - 0.63 | 8.2 | 100 | J7MN-12-E63 | 1 | 0.21 | |
0.8 | - | 0.55 - 0.8 | 10 | 100 | J7MN-12-E8 | 1 | 0.21 | |
1 | 0.25 | 0.7 - 1 | 13 | 100 | J7MN-12-1 | 1 | 0.21 | |
1.25 | 0.37 | 0.9 - 1.25 | 16 | 100 | J7MN-12-1E25 | 1 | 0.21 | |
1.6 | 0.55 | 1.1 - 1.6 | 21 | 100 | J7MN-12-1E6 | 1 | 0.21 | |
2 | 0.75 | 1.4 - 2 | 26 | 100 | J7MN-12-2 | 1 | 0.21 | |
2.5 | - | 1.8 - 2.5 | 33 | 100 | J7MN-12-2E5 | 1 | 0.21 | |
3.2 | 1.1 | 2.2 - 3.2 | 42 | 100 | J7MN-12-3E2 | 1 | 0.21 | |
4 | 1.5 | 2.8 - 4 | 52 | 100 | J7MN-12-4 | 1 | 0.21 | |
5 | - | 3.5 - 5 | 65 | 100 | J7MN-12-5 | 1 | 0.21 | |
6.3 | 2.2 | 4.5 - 6.3 | 82 | 100 | J7MN-12-6E3 | 1 | 0.21 | |
8 | 3 | 5.5 - 8 | 104 | 50 | J7MN-12-8 | 1 | 0.21 | |
10 | 4 | 7 - 10 | 130 | 50 | J7MN-12-10 | 1 | 0.21 | |
12 | 5.5 | 9 - 12 | 156 | 50 | J7MN-12-12 | 1 | 0.21 | |
Circuit-Breakers J7MN-25 | ||||||||
0.16 | - | 0.11 - 0.16 | 2.1 | 100 | J7MN-25-E16 | 1 | 0.32 | |
0.2 | - | 0.14 - 0.2 | 2.6 | 100 | J7MN-25-E2 | 1 | 0.32 | |
0.25 | 0.06 | 0.18 - 0.25 | 3.3 | 100 | J7MN-25-E25 | 1 | 0.32 | |
0.32 | 0.09 | 0.22 - 0.32 | 4.2 | 100 | J7MN-25-E32 | 1 | 0.32 | |
0.4 | - | 0.28 - 0.4 | 5.2 | 100 | J7MN-25-E4 | 1 | 0.32 | |
0.5 | 0.12 | 0.35 - 0.5 | 6.5 | 100 | J7MN-25-E5 | 1 | 0.32 | |
0.63 | 0.18 | 0.45 - 0.63 | 8.2 | 100 | J7MN-25-E63 | 1 | 0.32 | |
0.8 | - | 0.55 - 0.8 | 10 | 100 | J7MN-25-E8 | 1 | 0.32 | |
1 | 0.25 | 0.7 - 1 | 13 | 100 | J7MN-25-1 | 1 | 0.32 | |
1.25 | 0.37 | 0.9 - 1.25 | 16 | 100 | J7MN-25-1E25 | 1 | 0.32 | |
1.6 | 0.55 | 1.1 - 1.6 | 21 | 100 | J7MN-25-1E6 | 1 | 0.32 | |
2 | 0.75 | 1.4 - 2 | 26 | 100 | J7MN-25-2 | 1 | 0.32 | |
2.5 | - | 1.8 - 2.5 | 33 | 100 | J7MN-25-2E5 | 1 | 0.32 | |
3.2 | 1.1 | 2.2 - 3.2 | 42 | 100 | J7MN-25-3E2 | 1 | 0.32 | |
4 | 1.5 | 2.8 - 4 | 52 | 100 | J7MN-25-4 | 1 | 0.32 | |
5 | - | 3.5 - 5 | 65 | 100 | J7MN-25-5 | 1 | 0.32 | |
6.3 | 2.2 | 4.5 - 6.3 | 82 | 100 | J7MN-25-6E3 | 1 | 0.32 | |
8 | 3 | 5.5 - 8 | 104 | 100 | J7MN-25-8 | 1 | 0.32 | |
10 | 4 | 7 - 10 | 130 | 100 | J7MN-25-10 | 1 | 0.32 | |
12.5 | 5.5 | 9 - 12.5 | 163 | 100 | J7MN-25-12E5 | 1 | 0.32 | |
16 | 7.5 | 11 - 16 | 208 | 50 | J7MN-25-16 | 1 | 0.32 | |
20 | - | 14 - 20 | 260 | 50 | J7MN-25-20 | 1 | 0.32 | |
22 | - | 17 - 22 | 286 | 50 | J7MN-25-22 | 1 | 0.32 | |
25 | 11 | 20 - 25 | 325 | 50 | J7MN-25-25 | 1 | 0.32 | |
Circuit-Breakers J7MN-50 | ||||||||
25 | 11 | 18 - 25 | 325 | 50 | J7MN-50-25 | 1 | 0.96 | |
32 | 15 | 22 - 32 | 416 | 50 | J7MN-50-32 | 1 | 0.96 | |
40 | 18.5 | 28 - 40 | 520 | 50 | J7MN-50-40 | 1 | 0.96 | |
45 | - | 36 - 45 | 585 | 50 | J7MN-50-45 | 1 | 0.96 | |
50 | 22 | 40 - 50 | 650 | 50 | J7MN-50-50 | 1 | 0.96 | |
Circuit-Breakers J7MN-100 | ||||||||
63 | 30 | 45 - 63 | 819 | 50 | J7MN-100-63 | 1 | 2.1 | |
75 | 37 | 57 - 75 | 975 | 50 | J7MN-100-75 | 1 | 2.1 | |
90 | - | 70 - 90 | 1170 | 50 | J7MN-100-90 | 1 | 2.1 | |
100 | 45 | 80 - 100 *2 | 1235 | 50 | J7MN-100-100 | 1 | 2.1 |
*1. Recommended values for standard motors
*2. max. motor current 95A
Description | Version | for
circuit breaker |
Type | Pack
pcs. |
Weight
approx. kg/pcs. |
|
---|---|---|---|---|---|---|
Transverse auxiliary contact block | ||||||
Contact block | 1NO + 1NC | all | J73MN-11F | 10 | 0.02 | |
Auxiliary contact block for left hand side mounting (max 1pc. per circuit breaker) | ||||||
Contact block | 1NO + 1NC 9 mm | all | J73MN-11S | 10 | 0.03 | |
Signalling switch for left hand side mounting (max 1pc. per circuit breaker) | ||||||
Signalling switch | 1NO + 1NC each
Individual tripped and short-circuit signalling |
J7MN-25
J7MN-50 |
J73MN-T-11S | 1 | 0.07 | |
Auxiliary releases for right hand side mounting (max 1pc. per circuit breaker) | ||||||
Undervoltage release
Trips the circuit-breaker when the voltage is interrupted. Prevents the motor from being restarted accidentally when the voltage is restored, suitable for EMERGENCY STOP acc. to VDE 0113 |
AC 50 Hz
230 V AC 60 Hz 240 V |
all | J74MN-U-N1 | 1 | 0.12 | |
Shunt release
Trips the circuit-breaker when the release coil energized. |
50/60 Hz
100% ON 210-240 V 50/60 Hz, DC 5 sec ON 190-330 V |
J7MN-12 | J74MN-S-N2 | 1 | 0.11 |
Description | Version | for circuit
breaker |
Type | Pack
pcs. |
Weight
approx. kg/pcs. |
|
---|---|---|---|---|---|---|
Front Plates | ||||||
Moulded plastic front plate
with actuator diaphragm and holder for circuit breaker |
for actuation of circuit-
breakers in any enclosure protection degree IP55 |
J7MN-12 | J74MN-P12 | 1 | 0.08 | |
Moulded plastic front plate
with rotary operating mechanism lockable |
for actuation of circuit-
breakers in any enclosure protection degree IP55 |
J7MN-25
J7MN-50 |
J74MN-P25 | 1 | 0.08 | |
Holder for front plate
J74MN-P25 |
Holder is mounted on front
plate, circuit-breaker (with accessories) is snapped on |
J7MN-25 | J74MN-PH | 1 | 0.12 | |
Enclosures | ||||||
Moulded plastic enclose
with actuator diaphragm knockouts for J7MN-25 sealable |
protection degree IP55
with N- and PE- terminal (+ aux. contact + release) |
J7MN-12 | J74MN-PF12 | 1 | 0.27 | |
Moulded plastic enclose
with rotary operating mechanism knockouts for J7MN-25 lockable |
protection degree IP55
with N- and PE- terminal (+ aux. contact + release) |
J7MN-25 | J74MN-PF25 | 1 | 0.30 | |
Door-coupling mechanisms | ||||||
The door-coupling rotary operating mechanisms consist of a knob, a coupling driver and a extension
shaft (5 mm x 5 mm). The door-coupling rotary operating mechanisms are designed for degree of protection IP 65. The door locking device prevents accidental opening of the cubicle door in the ON position of the circuit- breaker. The OFF position can be locked with up to 3 padlocks. |
||||||
Door-coupling rotary
mechanism black |
extension shaft 330 mm
with supporting bracket |
J7MN-25 to
J7MN-50 |
J74MN-DC-B | 1 | 0.3 | |
Emergency-Stop
Door-coupling rotary mechanism red/yellow |
extension shaft 330 mm
with supporting bracket |
J7MN-25 to
J7MN-50 |
J74MN-DC-RY | 1 | 0.3 |
Description | Version | for
circuit breaker |
Type | Pack
pcs. |
Weight
approx. kg/pcs. |
|
---|---|---|---|---|---|---|
Insulated 3-phase busbar systems | ||||||
For feeding several modular circuit-breakers on standard mounting rails, insulated, shock-protected.
Rated operational voltage max. 690 V |
||||||
3-phase busbars
modular spacing 45 mm |
for 2 circuit-breakers | J7MN-12
J7MN-25 |
J74MN-L3-1/2 | 1 | 0.03 | |
for 3 circuit-breakers | J74MN-L3-1/3 | 1 | 0.05 | |||
for 4 circuit-breakers | J74MN-L3-1/4 | 1 | 0.07 | |||
for 5 circuit-breakers | J74MN-L3-1/5 | 1 | 0.10 | |||
For connecting the 3-phase busbars from circuit-breakers different sizes. Clamping together
J7MN-12 and J7MN-25 circuit-breakers is not possible due to the different modular spacings and the different heights of the terminals. |
||||||
Line side terminal
3-pole, connection from top |
Conductor cross-section
solid or stranded 6- 25 mm2 with ferrule 4-16 mm2 |
J7MN-12
J7MN-25 |
J74MN-TC12 | 1 | 0.04 | |
J74MN-TC25 | 1 | 0.04 | ||||
Shroud | for unused terminals | J7MN-12
J7MN-25 |
J74MN-DS | 20 | - |
Description | Version | for
circuit breaker |
Type | Pack
pcs. |
Weight
approx. kg/pcs. |
|
---|---|---|---|---|---|---|
DIN-rail adapters | ||||||
Adapter
for mechanical fixing of circuit-breaker and contactor |
35 mm-DIN-rail
(DIN EN50022) or screw mounting |
J7MN... | J74MN-HU | 10 | 0.05 | |
Link modules | ||||||
for electrical connection between circuit-breaker and contactor | ||||||
Link module | up to 20 A
up to 32 A |
J7MN... | J74MN-VD-12 | 10 | - | |
J74MN-VD-25 | 10 | - | ||||
Terminal block | ||||||
with increased creepage distances and clearances acc. to cULus Type „E" | ||||||
Terminal block | up to 600 V acc. to UL 489
not for transverse aux. contact block |
J7MN-25
J7MN-100 |
J74MN-TB25 | 1 | 0.12 | |
J74MN-TB100 | 1 | 0.15 |
last update: February 3, 2014