Relay Terminal (Vertical Type)
            
        
last update: April 10, 2017
The following specifications apply to G6D Relays mounted in a G70D Relay Terminal and not the G6D Relay itself.
| Rated voltage | 24 V DC | 
|---|---|
| Rated current | 10.5 mA | 
| Coil resistance | 2,880 Ω | 
| Must-operate voltage | 70% max. of rated voltage | 
| Must release voltage | 10% min. of rated voltage | 
| Max. voltage | 130% of rated voltage | 
| Power consumption | Approx. 200 mW | 
| Load | Resistive load (cosφ = 1) | |
|---|---|---|
| Rated load | 3 A at 250 V AC, 3 A at 30 V DC | |
| Rated carry current | 5 A *1 | |
| Max. switching voltage | 250 V AC, 30 V DC | |
| Max. switching current | 5 A | |
| Max. switching capacity
 (reference value)  | 
1,250 VA, 150 W | |
| Min. permissible load
 (reference value) *1  | 
5 V DC, 1 mA | |
| Endurance | Electrical | 100,000 operations min. (under and at the rated load at 1,800 operations/h) | 
| Mechanical | 20,000,000 operations min. (at 18,000 operations/h) | |
            *1. Up to 5 A can be carried when 8 or fewer outputs are ON.
*2. This value is for a switching frequency of 120 times per minute.
        
The following values apply to G3DZ Relays mounted in a G70D Output Block and not the G3DZ Relay itself.
| Rated voltage | 24 V DC | |
|---|---|---|
| Operating voltage | 19.2 to 28.8 V DC | |
| Voltage level | Must-operate | 19.2 V DC max. | 
| Must release | 1 V DC min. | |
| Input impedance | 4 kΩ±20% | |
| Rated current | 8.2 mA±20% | |
Note: The rated current includes the current consumption of the operation indicator.
| Load voltage | 3 to 264 V AC, 3 to 125 V DC | 
|---|---|
| Load current | 100 μA to 0.3 A | 
| Inrush current | 6 A (10 ms) | 
| Item | G70D-VSOC16 | G70D-VFOM16 | 
|---|---|---|
| Relay outputs | Power MOSFET Relay outputs | |
| Contact configuration | 16 points (SPST-NO × 16) | |
| Contact structure | Single | --- | 
| Contact resistance | 100 mΩ max. *1 | --- | 
| Isolation method | --- | Photocoupler | 
| Must-operate time | 10 ms max. *2 | 10 ms max. | 
| Release time | 10 ms max. *2 | 15 ms max. | 
| Output ON-resistance | --- | 2.4 Ω max. | 
| Open-circuit leakage current | --- | 10 μA max. (at 125 V DC) | 
| Max. switching frequency | Mechanical: 18,000 operations/h
 Rated load: 1,800 operations/h  | 
--- | 
| Insulation resistance | 100 MΩ min. (at 500 V DC) | |
| Dielectric strength | 2,000 V AC for 1 min between coil and
 contact  | 
2,000 V AC for 1 min between input and
 output terminals  | 
| Noise immunity | Power input (normal mode): 600 V for 10 min with a pulse width of 100 ns to 1 μs
 Power input (common mode): 1.5 kV for 10 min with a pulse width of 100 ns to 1 μs Input cable (coiling): 1.5 kV for 10 min with a pulse width of 100 ns to 1 μs Unit body (coiling): 600 V for 10 min with a pulse width of 100 ns to 1 μs  | 
|
| Vibration resistance | Destruction: 10 to 55 to 10 Hz, 0.5-mm amplitude (1.0-mm double)
 Malfunction: 10 to 55 to 10 Hz, 0.375-mm amplitude (0.75-mm double)  | 
|
| Shock resistance | Destruction: 300 m/s2, Malfunction: 100 m/s2 | |
| Operating voltage range | 24 V DC +10%/-15% | |
| Current consumption | Approx. 170 mA at 24 V DC *3 | Approx. 125 mA at 24 V DC *4 | 
| Cable length | Between block and controller: 5 m max. (reference value for AWG28)
 Between block and external device: Dependent on load  | 
|
| LED color | Operation indicator: orange | |
| Coil surge absorber | Diode (600 V, 1 A) | |
| Ambient temperature | Operating: -25 to 55°C (with no icing or condensation) | |
| Ambient humidity | Operating: 45% to 85% | |
| Mounting strength | No damage when 49 N pull load was applied for 1 s in all directions (except for 9.8 N in
 direction of rail)  | 
|
| Terminal strength | Tightening torque: 0.78 to 118 N·m
 Pull strength: 49 N for 1 min  | 
|
| Weight *5 | Approx. 280 g | |
last update: April 10, 2017