Power Relay
last update: November 6, 2023
| Rated voltage | Rated current | Coil resistance |
Must-operate voltage |
Must-release voltage |
Max. voltage |
Power consumption |
|
|---|---|---|---|---|---|---|---|
| AC | 24 VAC | 75 mA | --- | 75% max. of rated voltage |
15% min. of rated voltage |
110% of rated voltage |
Approx. 1.8 to 2.6 VA |
| 50 VAC | 36 mA | --- | |||||
| 100 to 120 VAC | 18 to 21.6 mA | --- | |||||
| 200 to 240 VDC | 9 to 10.8 mA | --- | |||||
| DC | 12 VDC | 167 mA | 72 Ω | 10% min. of rated voltage |
Approx. 2.0 W | ||
| 24 VDC | 83 mA | 288 Ω | |||||
| 48 VDC | 42 mA | 1,150 Ω | |||||
| 100 VDC | 20 mA | 5,000 Ω | |||||
| Item | Resistive load (cosφ = 1) | Inductive load (cosφ = 0.4) | Resistive load |
|---|---|---|---|
| Contact mechanism | Double break | ||
| Contact material | Ag alloy | ||
| Rated load | NO: 25 A at 220 VAC (1 A at 220 VAC)
NC: 8 A at 220 VAC (1 A at 220 VAC) |
NO: 25 A at 30 VDC
NC: 8 A at 30 VDC |
|
| Rated carry current | NO: 25 A (1 A)
NC: 8 A (1 A) |
||
| Max. switching voltage | 250 VAC | 125 VDC | |
| Max. switching current | NO: 25 A (1 A)
NC: 8 A (1 A) |
||
Note: The values in parentheses indicate values for a bifurcated contact.
| Contact resistance *2 | 100 mΩ max. |
|---|---|
| Operate time *3 | 50 ms max. |
| Release time *3 | 50 ms max. |
| Max. operating frequency | Mechanical: 1,800 operations/hr Electrical: 1,800 operations/hr |
| Insulation resistance *4 | 1,000 MΩ min. (at 500 VDC) |
| Dielectric strength | 4,000 VAC, 50/60 Hz for 1 min between coil and contacts 4,000 VAC, 50/60 Hz for 1 min between contacts of different polarity 2,000 VAC, 50/60 Hz for 1 min between contacts of same polarity |
| Impulse withstand voltage | 10,000 V between coil and contact (with 1.2 x 50 μs impulse wave) |
| Vibration resistance | Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude) Malfunction: NO: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude) NC: 10 to 26 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude) |
| Shock resistance | Destruction: 1,000 m/s2 Malfunction: NO: 100 m/s2, NC: 20 m/s2 |
| Endurance | Mechanical: 1,000,000 operations min. (at 1,800 operations/hr) Electrical: 100,000 operations min. (at 1,800 operations/hr) *5 |
| Error rate *6 | 100 mA at 24 VDC (bifurcated contact: 24 VDC 10 mA) |
| Ambient temperature | Operating: -25°C to 60°C (with no icing or condensation) |
| Ambient humidity | Operating: 5% to 85% |
| Weight | PCB terminal: approx. 140 g Screw terminal: approx. 165 g Quick-connect terminal:approx. 140 g |
The G7J satisfies the following international standards. Approval for some international markings and symbols are still pending, however, and information on them will be added when they are approved.
| Coil ratings | Contact ratings | Number of test operations | |
|---|---|---|---|
| 24 to 265 VAC
6 to 110 VDC |
NO contact | 25 A 277 VAC, Resistive | 30,000 |
| 25 A 120 VAC, General Use | |||
| 25 A 277 VAC, General Use | |||
| 25 A 240 VAC, General Use | 100,000 | ||
| 1.5 kW 120 VAC, Tungsten | 6,000 | ||
| 1.5 hp 120 VAC | 1,000 | ||
| 3 hp 240/265/277 VAC | |||
| 3-phase 3 hp 240/265/277 VAC | 30,000 | ||
| 3-phase 5 hp 240/265/277 VAC | |||
| 20FLA/120LRA 120 VAC | |||
| 17FLA/102LRA 277 VAC | |||
| TV-10 120 VAC | 25,000 | ||
| 25 A 30 VDC, Resistive | 30,000 | ||
| *1 A 277 VAC, General Use | 6,000 | ||
| NC contact | 8 A 277 VAC, Resistive | 30,000 | |
| 8 A 120 VAC, General Use | |||
| 8 A 277 VAC, General Use | |||
| 8 A 30 VDC, Resistive | |||
| *1 A 277 VAC, General Use | 6,000 | ||
Note: *These ratings are bifurcated contact ratings.
UL approval: UL508 for industrial control devices
CSA approval: CSA C22.2 No. 14 for industrial control devices
| Model | Contact ratings | |
|---|---|---|
| NO contact | NC contact | |
| G7J-4A-B(P) (T)-KM
G7J-2A2B(P) (T)-KM G7J-3A1B-B(P) (T)-KM |
25 A 240 VAC cosφ = 0.4
25 A 240 VAC cosφ = 1 25 A 30 VDC L/R ≥ 1 |
8 A 240 VAC cosφ = 0.4
8 A 240 VAC cosφ = 1 8 A 30 VDC L/R ≥ 1 |
Note: Ask your OMRON representative for details on specifications.
VDE approval: EN60255-1-00: 1997
EN60255-23: 1996
| Model | Contact ratings |
|---|---|
| NO contact | |
| G7J-4A-B(P) (T) (Z)-KM
G7J-2A2B(P) (T)-KM |
Class AC1: 25 A at 220 VAC
11.5 A at 380 to 480 VAC Class AC3: 11.5 A at 220 VAC and 8.5 A at 380 to 480 VAC *Class AC1: 1 A at 220 VAC |
| G7J-3A1B-B(P) (T) (Z)-KM |
Note: Ask your OMRON representative for details on specifications.
*This rating is the bifurcated contact rating.
KEMA approval: EN60947-4-1 for contacts
last update: November 6, 2023