Simple Solid State Contactors
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: January 5, 2022
| Item | DC-input models | AC-input models |
|---|---|---|
| Rated supply voltage | 12 to 24 VDC | 100 to 240 VAC (50/60 Hz) |
| Operating voltage range | 9.6 to 26.4 VDC | 75 to 264 VAC (50/60 Hz) |
| Rated input current
(impedance) |
15 mA max. (at 12 to 24 VDC) | 36 kΩ ±20% (100 to 240 VAC) |
| Must operate voltage | 9.6 VDC max. | 75 VAC max. |
| Must release voltage | 3.6 VDC min. | 20 VAC min. |
| Item | G3J-211BL, G3J-211BL-2 | G3J-205BL, G3J-205BL-2 | |
|---|---|---|---|
| Rated load voltage | 100 to 240 VAC (50/60 Hz) | ||
| Load voltage range | 75 to 264 VAC (50/60 Hz) | ||
| Rated carry current *3 | 11.1 A
(Ta = 40°C) |
4.8 A
(Ta = 40°C) |
|
| Min. load current | 0.1 A | ||
| Peak-value current resistivity | 350 A, 60 Hz, 1 cycle | 150 A, 60 Hz, 1 cycle | |
| Overload resistance | Refer to Safety Precautions for the G3J-T, G3J-S, and G3J. | ||
| Closed current
(effective value) |
AC3 | 111 A | 48 A |
| AC4 | 133.2 A | 57.6 A | |
| Breaking current
(effective value) |
AC3 | 88.8 A | 38.4 A |
| AC4 | 111 A | 48 A | |
| Applicable load | 3-phase inductive
motor (AC3 AC4 AC53-a) |
200 to 220 VAC, 2.2 kW, (11.1 A) | 200 to 220 VAC, 0.75 kW, (4.8 A) |
| Motors passing the AC3-class, AC4-class, and AC53-a-class switching
frequency test (Ta = 40°C) under conditions specified by OMRON. |
|||
| Single-phase
motor (AC3) *1 |
100 VAC, 0.4 kW (11.1 A)
200 VAC, 0.75 kW (8.8 A) |
100 VAC, 0.1 kW, (5.1 A)
200 VAC, 0.4 kW (5.5 A) *2 |
|
| Resistive load (AC1) | 100 to 240 VAC, 11.1 A | 100 to 240 VAC, 4.8 A | |
| Item | DC-input models | AC-input models |
|---|---|---|
| Operate time | 1 ms max. | 50 ms max. |
| Release time | 5/6 of the load power supply cycle time +
1 ms max. |
3/2 of the load power supply cycle time +
1 ms max. |
| Output ON-voltage drop | 1.6 VRMS max. | |
| Leakage current * | 10 mA max. (at 200 VAC) | |
| Insulation resistance | 100 MΩ min. (at 500 VDC) | |
| Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |
| Vibration resistance | Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude | |
| Shock resistance | Destruction: 294 m/s2 | |
| Ambient temperature | Operating: -20°C to 60°C (with no icing or condensation)
Storage: -30°C to 70°C (with no icing or condensation) |
|
| Ambient humidity | Operating: 45% to 85% | |
| Weight | Approx. 700 g | |
| Standards | UL (File No.E64562), CSA (File No.LR35535), CCC GB/T 14048.6 No. 2016010304855599,
IEC947-4-1 |
|
* With 2-element models, the S-phase leakage current will be larger by a factor of √3.
last update: January 5, 2022