* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.

Time Ranges

Rated time Time range Rated time Time range
1 s 0.1 to 1 s 3 min 0.3 to 3 min
3 s 0.3 to 3 s 5 min 0.5 to 5 min
5 s 0.5 to 5 s 10 min 1 to 10 min
10 s 1 to 10 s 30 min 3 to 30 min
30 s 3 to 30 s 60 min 6 to 60 min
60 s 6 to 60 s 3 hrs 0.3 to 3 hrs

Ratings

Rated supply voltage 24, 100 to 120 or 200 to 240 VAC (50/60 Hz);
12, 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption H3JA-8A
100 to 120 VAC: Approx. 2.6 VA (1.1 W) at 120 VAC
200 to 240 VAC: Approx. 5.0 VA (1.5 W) at 240 VAC
24 VAC: Approx. 1.0 VA (0.9 W) at 24 VAC
24 VDC: Approx. 0.8 W at 24 VDC
12 VDC: Approx. 0.5 W at 12 VDC
H3JA-8C
100 to 120 VAC: Approx. 2.4 VA (0.9 W) at 120 VAC
200 to 240 VAC: Approx. 4.1 VA (1.1 W) at 240 VAC
24 VAC: Approx. 1.2 VA (1.0 W) at 24 VAC
24 VDC: Approx. 0.8 W at 24 VDC
Control outputs H3JA-8A: 7 A at 250 VAC, resistive load
H3JA-8C: 5 A at 250 VAC, resistive load

Characteristics

Accuracy of operating
time
±2% max. (full scale)
Setting error ±7% max. (full scale) ±50 ms at 20°C
Influence of voltage ±2% max. (full scale)
Influence of temperature ±5% max. (full scale)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts,
and between contact-carrying and control circuit, and between contacts of different poles)
750 VAC, 50/60 Hz for 1 min (between non-continuous contacts: H3JA-8A)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts: H3JA-8C)
Impulse withstand
voltage
3 kV (between power terminals)
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
Noise immunity ±1.5 kV (between power terminals) and ±1.5 kV (between output terminals), square-wave
noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity Destruction: 8 kV
Malfunction: 6 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm double amplitude in 3 directions for 1 hour each.
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude in 3 directions for 10 minutes each.
Shock resistance Destruction: 1,000 m/s2
Malfunction: 100 m/s2
Ambient temperature Operating: -10°C to 55°C
Storage: -25°C to 65°C
Ambient humidity Operating: 35% to 85%
Life expectancy H3JA-8A
Mechanical: 10,000,000 operations min.
Electrical: 60,000 operations min. (7 A resistive load at 250 VAC, 360 operations/h)
H3JA-8C
Mechanical: 10,000,000 operations min.
Electrical: 100,000 operations min. (5 A resistive load at 250 VAC, 360 operations/h)
EMC (EMI)
Emission Enclosure: EN55011 Group 1 class B
Emission AC Mains: EN55011 Group 1 class B
Harmonic Current: EN61000-3-2
Voltage Fluctuation and Flickering: EN61000-3-3
(EMS)
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3), 8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz)
(level 3)
Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3), 1 kV control port
with capacitive clamp (level 3)
Immunity Surge: EN61000-4-5: 2 kV common mode (level 3), 1 kV differential mode (level 3)
Approved standard UL508 *, CSA C22.2 No. 14, conforms to EN61812-1 (Pollution degree 2)
Case color Light gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight H3JA-8A: Approx. 50 g
H3JA-8C: Approx. 60 g