G3R-I/O

I/O Solid State Relays

G3R-I/O

SSR with Plug-in Terminals The Same Shape as the G2R-1-S Power Relays

Ratings

Input Modules for Microloads

Input Side

Model Rated voltage Operating
voltage
Input current Must-operate
voltage
Must-release
voltage
G3R-IAZR1SN-UTU 100 to 240 VAC 60 to 264 VAC 15 mA max. 60 VAC max. 20 VAC min.
G3R-IDZR1SN-UTU 5 VDC 4 to 6 VDC 8 mA max. 4 VDC max. 1 VDC min.
G3R-IDZR1SN-UTU 12 to 24 VDC 6.6 to 32 VDC 6.6 VDC max. 3.6 VDC min.
G3R-IDZR1SN-1-UTU 5 VDC 4 to 6 VDC 4 VDC max. 1 VDC min.
G3R-IDZR1SN-1-UTU 12 to 24 VDC 6.6 to 32 VDC 6.6 VDC max. 3.6 VDC min.

Output Side

Model Load voltage Load current
G3R-IAZR1SN-UTU 4 to 32 VDC 0.1 to 100 mA
G3R-IDZR1SN-UTU
G3R-IDZR1SN-UTU
G3R-IDZR1SN-1-UTU
G3R-IDZR1SN-1-UTU

Output Modules for Standard Loads

Input Side

Model Rated voltage Operating
voltage
Input
current
Must-operate
voltage
Must-release
voltage
G3R-OA202SZN-UTU 5 to 24 VDC 4 to 32 VDC 15 mA max.
(at 25°C)
4 VDC max. 1 VDC min.
G3R-OA202SLN-UTU
G3R-ODX02SN-UTU 8mA max.
G3R-OD201SN-UTU

Output Side

Model Load voltage Load current *1 Surge withstand current
G3R-OA202SZN-UTU 75 to 264 VAC 0.05 to 2 A *2 30 A (60 Hz, 1 cycle)
G3R-OA202SLN-UTU
G3R-ODX02SN-UTU 4 to 60 VDC 0.01 to 2 A *2 8 A (10 ms)
G3R-OD201SN-UTU 40 to 200 VDC 0.01 to 1.5 A *2 8 A (10 ms)

*1. Depends on the ambient temperature. Refer to the reference data Load Current vs. Ambient Temperature Rating on
       Data Sheet for details.
*2. The minimum current value is for a temperature of 10°C or higher.

I/O External Display

Lineup includes Input Modules and Output Modules.
The I/O Module classification and AC/DC classification are also indicated in the markings on top of the Relay.

Marking Specifications
AC IN Input Modules for Microloads, AC input
DC IN Input Modules for Microloads, DC input
AC OUT Output Modules for Standard Loads, AC output
DC OUT Output Modules for Standard Loads, DC output

G3R-I/O Specifications 10

Characteristics

Input Modules for Microloads

Model G3R-IAZR1SN-UTU G3R-IDZR1SN-UTU G3R-IDZR1SN-1-UTU
Operation time 20 ms max. 0.1 ms max. 15 ms max.
Release time
Response frequency 10 Hz 1 kHz 10 Hz
Output ON voltage drop 1.6 V max.
Leakage current 5 μA max.
Insulation resistance 100 MΩ min. between I/O
Dielectric strength 4,000 VAC for 1 min. between I/O
Vibration resistance 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Shock resistance 1,000 m/s2
Storage temperature -30 to 100°C (with no icing)
Ambient operating temperature -30 to 80°C (with no icing)
Ambient operating humidity 45% to 85%
Weight Approx. 18 g

Output Modules for Standard Loads

Model G3R-OA202SZN-UTU G3R-OA202SLN-UTU G3R-ODX02SN-UTU G3R-OD201SN-UTU
Operation time 1/2 load power supply
cycle + 1 ms max.
1 ms max.
Release time 1/2 load power supply cycle + 1 ms max. 2 ms max.
Response frequency 20 Hz 100 Hz
Output ON voltage drop 1.6 V max. 2.5 V max.
Leakage current 1.5 mA max. 1 mA max.
Insulation resistance 100 MΩ min. between I/O
Dielectric strength 4,000 VAC for 1 min. between I/O
Vibration resistance 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Shock resistance 1,000 m/s2
Storage temperature -30 to 100°C (with no icing)
Ambient operating
temperature
-30 to 80°C (with no icing)
Ambient operating
humidity
45% to 85%
Weight Approx. 18 g

Accessories (Order Separately)

Socket Characteristics

Model Rated
carry
current
Dielectric strength nsulation
resistance *
Remarks
P2RF-05-PU 10 A Between contact terminals of same polarity: 1,000 VAC for
1 min
1,000 MΩ min.
Between coil and contact terminals: 4,000 VAC for 1 min
P2RFZ-05(-E) 10 A Between contact terminals of same polarity: 1,000 VAC for
1 min
1,000 MΩ min.
Between coil and contact terminals: 4,000 VAC for 1 min
P2R-05P 10 A Between contact terminals of same polarity: 1,000 VAC for
1 min
1,000 MΩ min.
Between coil and contact terminals: 4,000 VAC for 1 min
P2R-057P 10 A Between contact terminals of same polarity: 1,000 VAC for
1 min
1,000 MΩ min.
Between coil and contact terminals: 5,000 VAC for 1 min
P2R-05A 10 A Between contact terminals of same polarity: 1,000 VAC for
1 min
1,000 MΩ min.
Between ground terminals: 1,500 VAC for 1 min
Between coil and contact terminals: 4,000 VAC for 1 min

* The insulation resistance was measured with a 500-VDC insulation resistance meter at the same places as those used for
   measuring the dielectric strength.