PROFIBUS-DP slave unit
last update: February 5, 2014
Installation | Host PLC System | CJ1 |
---|---|---|
Maximum number of
Units per PLC system |
40 | |
Current consumption | 400 mA (maximum) at 5V DC from PLC power supply | |
Weight | 90 g (typical) | |
Environment | Storage temperature | -20°C to +70°C |
Operating temperature | 0°C to +55°C | |
Operating humidity | 10 to 90% (non-condensing) | |
Conformance to
EMC- and environmental standards |
EN50081-2
EN61131-2 |
|
User
Interface |
Switch settings | Special I/O Machine number (00-95) by 2 rotary switch
PROFIBUS-DP node address (00-99) by 2 rotary switches |
LED Indicators | Unit status: RUN (green LED), ERC (red LED)
Network status: COMM (green LED), BF (red LED) CPU status: ERH (red LED) |
|
PLC Interface | No. of CIO
words allocated |
PLC → Unit: 1 word control data
Unit → PLC: 1 word status data |
No. of DM
words allocated |
Unit → PLC: 8 words of Unit setup information | |
Amount of
I/O data per Unit |
Fixed:
2 words CIO area (one in, one out) for Unit status + control bits. 2 words status information from the host PLC, containing operation status and error code (read from location A400). This information will be sent to the PROFIBUS master: - as extended diagnostics, only at a change of data content. - optionally, attached to the I/O data, each PROFIBUS cycle. Variable: 2 user-defined areas for PROFIBUS I/O data, with the following restrictions: - Up to 100 words input in one PLC area (CIO, H, D, EM). - Up to 100 words output in one PLC area (CIO, H, D, EM). - Inputs+outputs must be 180 words or less |
last update: February 5, 2014