Selector Switches
            
        
last update: November 5, 2024
6 A 240 VAC, 10 A 120 VAC
            AC-15 3 A 240 VAC
DC-13 4 A 24 VDC
        
            AC-15 3 A 240 VAC
DC-13 4 A 24 VDC
        
UL1059 and UL486E (Push-In Plus terminal block type)
| Rated insulation voltage | 600 V | |||||
|---|---|---|---|---|---|---|
| Rated carry current | 10 A | |||||
| Rated voltage | 24 V | 120 V | 240 V | 380 V | 440 V | |
| AC at 50/60 Hz | Resistive load (AC-12) | 10 A | 10 A | 6 A | 2 A | 2 A | 
| Inductive load (AC-15) | 10 A | 6 A | 3 A | 1.9 A | 1.6 A | |
| DC | Resistive load (DC-12) | 8 A | 2.2 A | 1.1 A | --- | --- | 
| Inductive load (DC-13) | 4 A | 1.1 A | 0.55 A | --- | --- | |
| Rated voltage | Applied voltage | Rated current | 
|---|---|---|
| 6 VAC/DC | 6 VAC/DC ±10% | Approx. 11 mA (red, orange, yellow, or blue)
 Approx. 5 mA (white or green)  | 
								
| 12 VAC/DC | 12 VAC/DC ±10% | Approx. 12 mA (red, orange, yellow, or blue)
 Approx. 5 mA (white or green)  | 
								
| 24 VAC/DC | 24 VAC/DC ±10% | Approx. 12 mA (red, orange, yellow, or blue)
 Approx. 5 mA (white or green)  | 
								
| 100 VAC | 100 VAC ±10% | Approx. 12 mA (red, orange, yellow, or blue)
 Approx. 5 mA (white or green)  | 
								
| 110 VAC | 110 VAC ±10% | |
| 120 VAC | 100 to 130 VAC | |
| 200 VAC | 200 VAC ±10% | Approx. 12 mA (red, orange, yellow, or blue)
 Approx. 5 mA (white or green)  | 
								
| 220 VAC | 220 VAC ±10% | |
| 230 VAC | 230 VAC ±10% | |
| 240 VAC | 220 to 250 VAC | 
| Type | Selector Switches | ||
|---|---|---|---|
| Item | Non-lighted models | Lighted models | |
| Allowable
 operating frequency  | 
Mechanical | 30 operations/minute max. | |
| Electrical | 30 operations/minute max. | ||
| Insulation resistance | 100 MΩ min. (at 500 VDC) | Not available for lighting units | |
| Contact resistance | 100 mΩ max. (initial value) | ||
| Dielectric
 strength  | 
Between terminals of
 same polarity  | 
2,500 VAC at 50/60 Hz for 1 min.
 (initial value)  | 
Not available for lighting units | 
| Between each terminal
 and ground  | 
2,500 VAC at 50/60 Hz for 1 min. (initial value) | ||
| Vibration
 resistance  | 
Malfunction | 10 to 55 Hz, 1.5-mm double amplitude (malfunction within 1 ms) | |
| Shock
 resistance  | 
Malfunction | 1,000 m/s2 max. (malfunction within 1 ms) | |
| Durability | Mechanical | 500,000 operations min. (Switches with 3 positions: 300,000 operations min.) | |
| Electrical | 500,000 operations min. (Switches with 3 positions: 300,000 operations min.)
 (250 VAC, 3 A, with an inductive load having power factor cos θ = 0.4)  | 
||
| Ambient operating temperature *1 | -25 to 70°C | -25 to 55°C | |
| Ambient operating humidity | 35% to 85% RH | ||
| Ambient storage temperature *1 | -40 to 80°C | ||
| Degree of protection *2 | Compliant with IEC IP66, Certified for UL508 Type 4X, 13 | ||
| Electric shock protection class | Class II | ||
| PTI (tracking characteristic) | 175 | ||
| Degree of contamination (application
 environment)  | 
3 (EN 60947-5-1) | ||
| Weight | Approx. 50 g (for 1NC/1NO) | Approx. 60 g (for 1NC/1NO) | |
            *1. With no icing or condensation.
*2. Degree of protection from the front of the panel.
        
| Type | Selector Switches | |
|---|---|---|
| Item | Manual reset | Automatic reset | 
| Total travel force (torque) (maximum TTF) | 0.6 Nm | 0.6 Nm | 
| Total travel (TT) | 2 positions: Approx. 90°, 3 positions: Approx. 45° | |
| Resetting force (torque) (RF) | 0.5 N·m max. | --- | 
       
    
| Selector Switches | ||||
|---|---|---|---|---|
| 2 positions | 3 positions | |||
| Lighted | Non-lighted | Lighted | Non-lighted | |
| Linking example | ![]()  | 
										
											
											 
											*  | 
										![]()  | 
										![]()  | 
									
last update: November 5, 2024