DIN Track Terminal Blocks with Screw Terminals
last update: August 19, 2024
Model | XW5T-S2.5-1.1-1(BL) | XW5T-S4.0-1.1-1(BL) | XW5T-S6.0-1.1-1(BL) | XW5T-S10-1.1-1(BL) | |
---|---|---|---|---|---|
Appearance and internal
wiring |
1 tier, 1:1
![]() |
1 tier, 1:1
![]() |
1 tier, 1:1
![]() |
1 tier, 1:1
![]() |
|
Applicable
wire sizes |
NOMINAL CROSS
SECTION |
2.5 mm2 | 4.0 mm2 | 6.0 mm2 | 10 mm2 |
Minimum conductor
cross section solid |
0.14 mm2 | 0.14 mm2 | 0.2 mm2 | 0.5 mm2 | |
Maximum conductor
cross section solid |
4.0 mm2 | 6.0 mm2 | 10 mm2 | 16 mm2 | |
Minimum conductor
cross section fine stranded |
0.14 mm2 | 0.14 mm2 | 0.2 mm2 | 0.5 mm2 | |
Maximum conductor
cross section fine stranded |
4.0 mm2 | 6.0 mm2 | 10 mm2 | 16 mm2 | |
Minimum conductor
cross section (flex., stranded) with cable end sleeve |
0.5 mm2 | 0.5 mm2 | 0.5 mm2 | 0.5 mm2 | |
Maximum conductor
cross section (flex., stranded) with cable end sleeve |
2.5 mm2 | 4.0 mm2 | 6.0 mm2 | 10 mm2 | |
Conductor cross
section AWG |
AWG26 to AWG12 | AWG26 to AWG10 | AWG24 to AWG8 | AWG20 to AWG6 | |
Wire strip length | 9 mm | 9 mm | 11 mm | 13 mm | |
Tightening torque | 0.4 Nm | 0.5 Nm | 1.2 Nm | 1.2 Nm | |
Dimensions | 5×48.2×56 | 6×48.2×56 | 8×48.2×56 | 10×48.2×56.2 | |
Mounting rail | TH35 | TH35 | TH35 | TH35 | |
IEC rated voltage | 1,000 V | 1,000 V | 1,000 V | 1,000 V | |
IEC rated current | 24 A | 32 A | 41 A | 57 A | |
Rated impulse voltage | 8 kV | 8 kV | 8 kV | 8 kV | |
UL rated voltage | 600 V | 600 V | 600 V | 600 V | |
UL rated current | 20 A | 30 A | 50 A | 65 A | |
End Covers | XW5E-S2.5-1.1-1 | XW5E-S2.5-1.1-1 | XW5E-S2.5-1.1-1 | XW5E-S2.5-1.1-1 | |
Applicable nameplates | XW5Z-S2.5LB | XW5Z-S4.0LB[] | XW5Z-S6.0LB[] | --- | |
Applicable Short Bars | XW5S-S4.0-[]
([]: Poles = 2, 3, 4, 5 or 10) |
XW5S-S4.0-[]
([]: Poles = 2, 3, 4, 5 or 10) |
XW5S-S6.0-[]
([]: Poles = 2,3, 4, or 5) |
XW5S-S10-[]
([]: Poles = 2) |
Model | XW5T-S16-1.1-1(BL) | XW5T-S35-1.1-1(BL) | XW5T-S150-1.1-1(BL) | |
---|---|---|---|---|
Appearance and internal
wiring |
1 tier, 1:1
![]() |
1 tier, 1:1
![]() |
1 tier, 1:1
![]() |
|
Applicable
wire sizes |
NOMINAL CROSS
SECTION |
16 mm2 | 35 mm2 | 150 mm2 |
Minimum conductor
cross section solid |
1.5 mm2 | 10 mm2 | --- | |
Maximum conductor
cross section solid |
16 mm2 | 10 mm2 | --- | |
Minimum conductor
cross section fine stranded |
4.0 mm2 | 10 mm2 | 35 mm2 | |
Maximum conductor
cross section fine stranded |
25 mm2 | 35 mm2 | 150 mm2 | |
Minimum conductor
cross section (flex., stranded) with cable end sleeve |
1.5 mm2 | --- | --- | |
Maximum conductor
cross section (flex., stranded) with cable end sleeve |
16 mm2 | --- | --- | |
Conductor cross
section AWG |
AWG14 to AWG4 | AWG10 to AWG 1/0 | AWG 2/0 to 350 kcmil | |
Wire strip length | 15 mm | 18 mm | 30 mm | |
Tightening torque | 2 Nm | 3 Nm | 10 Nm | |
Dimensions | 12×58.5×62 | 16×63×75.1 | 28×96×106.1 | |
Mounting rail | TH35 | TH35 | TH35 | |
IEC rated voltage | 1,000 V | 800 V | 1,000 V | |
IEC rated current | 76 A | 124 A | 309 A | |
Rated impulse voltage | 8 kV | 8 kV | 8 kV | |
UL rated voltage | 600 V | 600 V | 600 V | |
UL rated current | 85 A | 150 A | 335 A | |
End Covers | XW5E-S16 | |||
Applicable nameplates | --- | --- | --- | |
Applicable Short Bars | XW5S-S16-[] ([]: Poles = 2) | --- | --- |
Model | XW5T-S2.5-1.1-2 | XW5T-S2.5-1.1-2V | XW5T-S4.0-1.2-1(BL) | |
---|---|---|---|---|
Appearance and internal
wiring |
2 tier, 1:1
![]() |
2 tier, 1:1
![]() |
1 tier, 1:2
![]() |
|
Applicable
wire sizes |
NOMINAL CROSS
SECTION |
2.5 mm2 | 2.5 mm2 | 4.0 mm2 |
Minimum conductor
cross section solid |
0.2 mm2 | 0.2 mm2 | 0.14 mm2 | |
Maximum conductor
cross section solid |
4.0 mm2 | 4.0 mm2 | 6.0 mm2 | |
Minimum conductor
cross section fine stranded |
0.14 mm2 | 0.14 mm2 | 0.14 mm2 | |
Maximum conductor
cross section fine stranded |
2.5 mm2 | 2.5 mm2 | 6.0 mm2 | |
Minimum conductor
cross section (flex., stranded) with cable end sleeve |
--- | --- | 0.5 mm2 | |
Maximum conductor
cross section (flex., stranded) with cable end sleeve |
--- | --- | 4.0 mm2 | |
Conductor cross
section AWG |
AWG22 to AWG12 | AWG22 to AWG12 | AWG26 to AWG10 | |
Wire strip length | 8 mm | 8 mm | 9 mm | |
Tightening torque | 0.4 Nm | 0.4 Nm | 0.5 Nm | |
Dimensions | 5×65.8×71.4 | 5×65.8×71.4 | 6×58×56 | |
Mounting rail | TH35 | TH35 | TH35 | |
IEC rated voltage | 500 V | 500 V | 500 V | |
IEC rated current | 24 A | 24 A | 32 A | |
Rated impulse voltage | 6 kV | 6 kV | 6 kV | |
UL rated voltage | 600 V | 600 V | 300 V | |
UL rated current | 20 A | 20 A | 30 A | |
End Covers | XW5E-S2.5N | XW5E-S2.5N | XW5E-S4.0-1.2-1 | |
Applicable nameplates | XW5Z-2.5LB[] | XW5Z-2.5LB[] | XW5Z-4.0LB[] | |
Applicable Short Bars | XW5S-S2.5-[]N
([]: Poles = 2, 3, 4, 5, or 10) |
XW5S-S2.5-[]N
([]: Poles = 2, 3, 4, 5, or 10) |
XW5S-S4.0-[]
([]: Poles = 2, 3, 4, 5, or 10) |
Model | XW5T-S4.0-2.2-1(BL) | XW5T-S4.0-1.1-2 | XW5T-S4.0-1.1-2V | |
---|---|---|---|---|
Appearance and internal
wiring |
1 tier, 2:2
![]() |
2 tier, 1:1
![]() |
2 tier, 1:1
![]() |
|
Applicable
wire sizes |
NOMINAL CROSS
SECTION |
4.0 mm2 | 4.0 mm2 | 4.0 mm2 |
Minimum conductor
cross section solid |
0.14 mm2 | 0.14 mm2 | 0.14 mm2 | |
Maximum conductor
cross section solid |
6.0 mm2 | 6.0 mm2 | 6.0 mm2 | |
Minimum conductor
cross section fine stranded |
0.14 mm2 | 0.14 mm2 | 0.14 mm2 | |
Maximum conductor
cross section fine stranded |
6.0 mm2 | 6.0 mm2 | 6.0 mm2 | |
Minimum conductor
cross section (flex., stranded) with cable end sleeve |
0.5 mm2 | 0.5 mm2 | 0.5 mm2 | |
Maximum conductor
cross section (flex., stranded) with cable end sleeve |
4.0 mm2 | 4.0 mm2 | 4.0 mm2 | |
Conductor cross
section AWG |
AWG26 to AWG10 | AWG26 to AWG10 | AWG26 to AWG10 | |
Wire strip length | 9 mm | 9 mm | 9 mm | |
Tightening torque | 0.5 Nm | 0.5 Nm | 0.5 Nm | |
Dimensions | 6×69×58 | 6×73×75 | 6×73×75 | |
Mounting rail | TH35 | TH35 | TH35 | |
IEC rated voltage | 500 V | 800 V | 800 V | |
IEC rated current | 32 A | 32 A | 32 A | |
Rated impulse voltage | 6 kV | 8 kV | 8 kV | |
UL rated voltage | 300 V | 300 V | 300 V | |
UL rated current | 30 A | 30 A | 30 A | |
End Covers | XW5E-S4.0-2.2-1 | XW5E-S4.0-1.1-2 | XW5E-S4.0-1.1-2 | |
Applicable nameplates | XW5Z-4.0LB[] | XW5Z-4.0LB[] | XW5Z-4.0LB[] | |
Applicable Short Bars | XW5S-S4.0-[]
([]: Poles = 2, 3, 4, 5, or 10) |
XW5S-S4.0-[]
([]: Poles = 2, 3, 4, 5, or 10) |
XW5S-S4.0-[]
([]: Poles = 2, 3, 4, 5, or 10) |
Model | XW5G-S2.5-1.1-1 | XW5G-S4.0-1.1-1 | XW5G-S6.0-1.1-1 | XW5G-S10-1.1-1 | |
---|---|---|---|---|---|
Appearance and internal
wiring |
1 tier, 1:1
![]() |
1 tier, 1:1
![]() |
1 tier, 1:1
![]() |
1 tier, 1:1
![]() |
|
Applicable
wire sizes |
NOMINAL CROSS
SECTION |
2.5 mm2 | 4.0 mm2 | 6.0 mm2 | 10 mm2 |
Minimum conductor
cross section solid |
0.14 mm2 | 0.14 mm2 | 0.2 mm2 | 0.5 mm2 | |
Maximum conductor
cross section solid |
4.0 mm2 | 6.0 mm2 | 10 mm2 | 16 mm2 | |
Minimum conductor
cross section fine stranded |
0.14 mm2 | 0.14 mm2 | 0.2 mm2 | 0.5 mm2 | |
Maximum conductor
cross section fine stranded |
4.0 mm2 | 6.0 mm2 | 10 mm2 | 16 mm2 | |
Minimum conductor
cross section (flex., stranded) with cable end sleeve |
0.5 mm2 | 0.5 mm2 | 0.5 mm2 | 0.5 mm2 | |
Maximum conductor
cross section (flex., stranded) with cable end sleeve |
2.5 mm2 | 4.0 mm2 | 6.0 mm2 | 10 mm2 | |
Conductor cross
section AWG |
AWG26 to AWG12 | AWG26 to AWG10 | AWG24 to AWG8 | AWG20 to AWG6 | |
Wire strip length | 9 mm | 9 mm | 11 mm | 13 mm | |
Tightening torque | 0.4 Nm | 0.5 Nm | 1.2 Nm | 1.2 Nm | |
Dimensions | 5×48.2×56 | 6×48.2×56 | 8×48.2×56 | 10×48.2×56.2 | |
Mounting rail | TH35 | TH35 | TH35 | TH35 | |
IEC rated voltage | 1,000 V | 1,000 V | 1,000 V | 1,000 V | |
IEC rated current | --- | --- | --- | --- | |
Rated impulse voltage | 8 kV | 8 kV | 8 kV | 8 kV | |
UL rated voltage | 600 V | 600 V | 600 V | 600 V | |
UL rated current | --- | --- | --- | --- | |
End Covers | XW5E-S2.5 | XW5E-S2.5 | XW5E-S2.5 | XW5E-S2.5 | |
Applicable nameplates | XW5Z-S2.5LB[] | XW5Z-S4.0LB[] | XW5Z-S6.0LB[] | --- | |
Applicable Short Bars | --- | --- | --- | --- |
Model | XW5G-S16-1.1-1 | XW5G-S35-1.1-1 | |
---|---|---|---|
Appearance and internal
wiring |
1 tier, 1:1
![]() |
1 tier, 1:1
![]() |
|
Applicable
wire sizes |
NOMINAL CROSS
SECTION |
16 mm2 | 35 mm2 |
Minimum conductor
cross section solid |
1.5 mm2 | 10 mm2 | |
Maximum conductor
cross section solid |
16 mm2 | 35 mm2 | |
Minimum conductor
cross section fine stranded |
4.0 mm2 | 10 mm2 | |
Maximum conductor
cross section fine stranded |
25 mm2 | 35 mm2 | |
Minimum conductor
cross section (flex., stranded) with cable end sleeve |
1.5 mm2 | --- | |
Maximum conductor
cross section (flex., stranded) with cable end sleeve |
16 mm2 | --- | |
Conductor cross
section AWG |
AWG14 to AWG4 | AWG10 to AWG2 | |
Wire strip length | 15 mm | 20 mm | |
Tightening torque | 2 Nm | 3 Nm | |
Dimensions | 12×58.5×62 | 16×63×75.1 | |
Mounting rail | TH35 | TH35 | |
IEC rated voltage | 1000 V | 800 V | |
IEC rated current | --- | --- | |
Rated impulse voltage | 8 kV | 8 kV | |
UL rated voltage | 600 V | 600 V | |
UL rated current | --- | --- | |
End Covers | XW5E-S16 | --- | |
Applicable nameplates | --- | --- | |
Applicable Short Bars | --- | --- |
Model | XW5G-S4.0-2.2-1 | |
---|---|---|
Appearance and internal
wiring |
1 tier, 2:2
![]() |
|
Applicable
wire sizes |
NOMINAL CROSS SECTION | 4.0 mm2 |
Minimum conductor cross section solid | 0.14 mm2 | |
Maximum conductor cross section solid | 6 mm2 | |
Minimum conductor cross section fine stranded | 0.14 mm2 | |
Maximum conductor cross section fine stranded | 6 mm2 | |
Minimum conductor cross section
(flex., stranded) with cable end sleeve |
0.5 mm2 | |
Maximum conductor cross section
(flex., stranded) with cable end sleeve |
4 mm2 | |
Conductor cross section AWG | AWG26 to AWG10 | |
Wire strip length | 9 mm | |
Tightening torque | 0.5 Nm | |
Dimensions | 6×69×58 | |
Mounting rail | TH35 | |
IEC rated voltage | 500 V | |
IEC rated current | --- | |
Rated impulse voltage | 6 kV | |
UL rated voltage | 300 V | |
UL rated current | --- | |
End Covers | XW5E-S4.0-2.2-1 | |
Applicable nameplates | XW5Z-4.0LB[] | |
Applicable Short Bars | --- |
Model | XW5T-S4.0-FU5 | XW5T-S4.0-FU6 | |
---|---|---|---|
Appearance and internal wiring | 1 tier, 1:1
![]() |
1 tier, 1:1
![]() |
|
Applicable
wire sizes |
NOMINAL CROSS SECTION | 4.0 mm2 | 4.0 mm2 |
Minimum conductor cross
section solid |
0.5 mm2 | 0.5 mm2 | |
Maximum conductor cross
section solid |
6 mm2 | 6 mm2 | |
Minimum conductor cross
section fine stranded |
0.5 mm2 | 0.5 mm2 | |
Maximum conductor cross
section fine stranded |
4 mm2 | 4 mm2 | |
Minimum conductor cross
section (flex., stranded) with cable end sleeve |
--- | --- | |
Maximum conductor cross
section (flex., stranded) with cable end sleeve |
--- | --- | |
Conductor cross section AWG | AWG22 to AWG10 | AWG22 to AWG10 | |
Wire strip length | 8 mm | 8 mm | |
Tightening torque | 0.5 Nm | 0.5 Nm | |
Dimensions | 8×77.2×62 | 10×77.2×62 | |
Mounting rail | TH35 | TH35 | |
IEC rated voltage | 800 V | 800 V | |
IEC rated current | 6.3 A | 10 A | |
Rated impulse voltage | 8 kV | 8 kV | |
UL rated voltage | 600 V | 600 V | |
UL rated current | 15 A | 15 A | |
End Covers | --- | --- | |
Applicable nameplates | --- | --- | |
Applicable Short Bars | --- | --- |
The fuse blocks of this type have a flip top disconnect lever. It accepts miniature fuses of 5×20, 5×25 and 5×30 mm (terminal width: 8 mm) or 6.3×32 mm (terminal width: 10 mm). The hinged lever has latch points both in the open and in the closed position, and can be sealed.
Depending on the application and the installation method, the circumstances for increased temperature must be checked in the closed fuse holders. Higher ambient temperatures are an additional load for the fuse inserts. Therefore, the reduction of the rated current must be considered accordingly in these applications.
Model | XW5T-S4.0-KD | |
---|---|---|
Appearance and internal wiring | 1 tier, 1:1
![]() |
|
Applicable
wire sizes |
NOMINAL CROSS SECTION | 4.0 mm2 |
Minimum conductor cross
section solid |
0.14 mm2 | |
Maximum conductor cross
section solid |
6 mm2 | |
Minimum conductor cross
section fine stranded |
0.14 mm2 | |
Maximum conductor cross
section fine stranded |
6 mm2 | |
Minimum conductor cross
section (flex., stranded) with cable end sleeve |
0.5 mm2 | |
Maximum conductor cross
section (flex., stranded) with cable end sleeve |
4 mm2 | |
Conductor cross section AWG | AWG26 to AWG10 | |
Wire strip length | 9 mm | |
Tightening torque | 0.5 Nm | |
Dimensions | 6×58×58 | |
Mounting rail | TH35 | |
IEC rated voltage | 500 V | |
IEC rated current | 20 A | |
Rated impulse voltage | 6 kV | |
UL rated voltage | 300 V | |
UL rated current | 16 A | |
End Covers | XW5E-S4.0-1.2-1 | |
Applicable nameplates | XW5Z-S4.0LB[] | |
Applicable Short Bars | XW5S-S4.0-[] |
Model | XW5S-S2.5-[] | XW5S-S4.0-[] | XW5S-S6.0-[] | XW5S-S10-[] | XW5S-S16-[] |
---|---|---|---|---|---|
IEC rated voltage | 600 V | 1,000 V | |||
IEC rated current | 20 A | 30 A | 50 A | 57 A | 76 A |
UL rated voltage | 600 V | ||||
UL rated current | 20 A | 30 A | 50 A | 65 A | 85 A |
Compliant standards | UL | ||||
IEC60947-7-1 |
Operating temperature range | 40 to 60°C (with no condensation or icing) |
---|---|
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Operating humidity | range 5% to 95% |
Compliant standards | cULus (UL 1059), IEC 60947-7-1 and IEC 60947-7-2 |
Vibration resistance | 5 to 150 Hz 0.964 (m/s2)2/Hz |
Shock resistance | 50 m/s2 30 ms according EN 61373 |
last update: August 19, 2024