Safety CPU Unit
last update: October 2, 2023
Certification body | Standards |
---|---|
TÜV Rheinland | • EN ISO 13849-1
• EN ISO 13849-2 • IEC 61508 parts 1-7 • IEC/EN 61131-2 • IEC 61326-3-1 • IEC 61131-6 |
UL | • NRAG (UL 61010-1 and UL 61010-2-201 and UL 121201)
• NRAG7 (CSA C22.2 No. 61010-1 and CSA C22.2 No. 61010-2-201 and CSA C22.2 No. 213) • FSPC (IEC 61508 and ISO 13849) |
Shipbuilding Standards | NK, LK |
Using the NX-series Safety CPU Unit allows you to build a safety control system that meets the following standards:
• Requirements for SIL 3 in IEC 61508
• Requirements for PLe and Category 4 in EN ISO 13849-1
The NX-series Safety CPU Units are also registered for RCM, EAC, and KC compliance.
Item | Specification | |
---|---|---|
Enclosure | Mounted in a panel (open) | |
Grounding method | Ground to 100 Ω or less | |
Operating
environment |
Ambient operating temperature | 0 to 55°C |
Ambient operating humidity | 10% to 95% (with no condensation or icing) | |
Atmosphere | Must be free from corrosive gases. | |
Ambient storage temperature | -25 to 70°C (with no condensation or icing) | |
Altitude | 2,000 m max. | |
Pollution degree | 2 or less | |
Noise immunity | Conforms to IEC 61131-2.
2 kV on power supply line |
|
Insulation class | Class III (SELV) | |
Overvoltage category | II | |
EMC immunity level | Zone B | |
Vibration resistance | Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude 8.4 to 150 Hz, acceleration of 9.8 m/s2 100 minutes each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) |
|
Shock resistance | Conforms to IEC 60068-2-27.
147 m/s2, 3 times each in X, Y, and Z directions |
|
Insulation resistance | 20 MΩ between isolated circuits (at 100 VDC) | |
Dielectric strength | 510 VAC for 1 min between isolated circuits,
leakage current: 5 mA max. |
|
Installation method | DIN Track (IEC 60715 TH35-7.5/TH35-15) |
Unit name | Safety CPU Unit | |
---|---|---|
Model | NX-SL5500 | NX-SL5700 |
Maximum number of safety
I/O points |
1024 points | 2032 points |
Program capacity | 2048 KB | 4096 KB |
Number of safet master
connections *1 |
128 | 254 |
Number of CIP Safety
originator connections |
128 | 254 |
Number of CIP Safety target
connections |
4 | 4 |
Number of originators
that can be connected with a multi-cast connection |
8 | 8 |
Number of FSoE maste
connections |
128 | 254 |
I/O refreshing method | Free-Run refreshing | |
External connection terminals | None | |
Indicators | ![]() |
![]() |
Hardware switch settings | ![]() |
![]() |
Dimensions | 30 × 100 × 71 mm (W × H × D) | |
I/O power supply method | Not supplied. | |
Current capacity of I/O power
supply terminals |
No I/O power supply terminals | |
NX Unit power consumption *2 | 3.35 W max. | |
Current consumption from
I/O power supply |
No consumption | |
Weight | 130 g max. | |
Installation orientation and
restrictions *3 |
Installation orientation: Upright installation
Restriction: None. |
The following table shows the NX-series CPU Unit, Communications Units, and Sysmac Studio editions that can be used with the NX-SL5[][][] Safety CPU Unit.
CPU Unit and
Communications Unit |
NJ/NX Series
CPU Unit *1 |
Communications Unit | ||
---|---|---|---|---|
NX102-[][][][]
NX502-[][][][] |
EtherCAT Coupler Unit
NX-ECC20[] |
EtherNet/IP Coupler
Unit NX-EIC202 |
Communication
Control Unit NX-CSG320 |
|
Edition of
Sysmac Studio *2 |
Standard Edition | Standard Edition | Standard Edition
Sysmac Studio Safety Edition |
Standard Edition
Sysmac Studio Safety Edition |
NX-SL5500 | YES | No | No | YES |
NX-SL5700 | YES | No | No | YES |
The following table shows the possible combinations of versions of NX-series Safety Control Units, CPU Units, Communication Control Units, and Sysmac Studio. Available functions that are related to safety control vary depending on the versions of the units and Sysmac Studio. Refer to the NX-series Safety Control Unit User's Manual (Cat. No. Z930) and the NX-series Safety Control Unit/Communication Control Unit User's Manual (Cat. No. Z395) for details.
NX-SL5[][][] version 1.4 can be connected to the following versions of the CPU Unit or Communication Control Unit:
• NX102 CPU Unit version 1.31 or later and Sysmac Studio version 1.40 or higher
• NX502 CPU Unit version 1.60 or later and Sysmac Studio version 1.54 or higher
• NX-CSG version 1.01 or later and Sysmac Studio version 1.40 or higher
Safety Control Unit
model and version |
NX bus master:
NX102 CPU Unit |
NX bus master:
NX502 CPU Unit |
NX bus master:
Communication Control Unit |
||||
---|---|---|---|---|---|---|---|
Model | Unit
Version |
NX102-[][][][] | Sysmac Studio | NX502-[][][][]
*1 |
Sysmac Studio
*2 |
Communication
Control Unit NX-CSG |
Sysmac Studio |
NX-SL5500 | Ver.1.3 | Ver.1.31 or later | Ver.1.24 or
higher |
Ver.1.60 or later | Ver.1.54 or
higher |
Ver.1.01 or later | Ver.1.24 or higher |
Ver.1.4 | Ver.1.40 or
higher |
Ver.1.40 or higher | |||||
NX-SL5700 | Ver.1.2 | --- | --- | --- | --- | Ver.1.00 only | Ver.1.24 or higher |
Ver.1.3 | Ver.1.31 or later | Ver.1.24 or
higher |
Ver.1.60 or
later |
Ver.1.54 or
higher |
Ver.1.01 or later | Ver.1.24 or higher | |
Ver.1.4 | Ver.1.31 or later | Ver.1.40 or
higher |
Ver.1.60 or
later |
Ver.1.54 or
higher |
Ver.1.01 or later | Ver.1.40 or higher | |
NX-SIH400 | Ver.1.0 | Ver.1.30 or later | Ver.1.22 or
higher |
Ver.1.60 or
later |
Ver.1.54 or
higher |
Ver.1.00 or later | Ver.1.24 or higher |
Ver.1.1 | Ver.1.24 or higher | ||||||
NX-SID800 | Ver.1.0 | Ver.1.30 or later | Ver.1.22 or
higher |
Ver.1.60 or
later |
Ver.1.54 or
higher |
Ver.1.00 or later | Ver.1.24 or higher |
NX-SOH200 | Ver.1.0 | Ver.1.30 or later | Ver.1.22 or
higher |
Ver.1.60 or
later |
Ver.1.54 or
higher |
Ver.1.00 or later | Ver.1.24 or higher |
NX-SOD400 | Ver.1.0 | Ver.1.30 or later | Ver.1.22 or
higher |
Ver.1.60 or
later |
Ver.1.54 or
higher |
Ver.1.00 or later | Ver.1.24 or higher |
*1. To use CIP Safety communications, connect the NX-EIP201 EtherNet/IP Unit to the NX502 CPU Unit or use the NX502-1[]00 CPU Unit version 1.64 or later.
*2. Use the Sysmac Studio version 1.56 or higher for CIP Safety communications via the built-in EtherNet/IP port on the NX502-1[]00 version 1.64 or later.
last update: October 2, 2023